| 09/20/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/18/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL METAL RACEWAY BETWEEN SERVICE PANEL 1/2" EMT TO BE METALLICALLY JAMED TOGETHER INTO A CONTINOUS ELECTRIC CONDUCTOR. NEC 300.10, 250.4, 250.118 2) INSTALL COVER ON JUNCTION BOX TO ? OF SERVICE PANEL |