Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio FINISH PREVIOUS ITEMS - PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
| 10/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL INSPECTION ITEMS FOR INSPECTION ON 10/5/07 2. CANNOT HAVE CONDUCTORS OF DISSIMILAR METALS INTERMIXED IN SPLICE CONNECTION NEC 110.14 |
|
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DOOR MUST OPEN 90 DEG. 2. CIRCUIT DIRECTORY TO BE AS PER 408.4 - NO GENERAL LABELING OR ABBREVIATIONS 3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE 4. CHANGE NIPPLE NOT AN APPROVED FITTING WITH LB 5. INSTALL MAIN BONDING JUMPER 6. OPEN TAPE TO INSPECT SPLICE CONNECTIONS 7. INSTALL ALL STRANDS UNDER TERMINAL STRIP 8. TIGHTEN LOOSE FITTINGS 9. VERIFY GAS OR WATER BOND |