Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01670
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ADDRESS CABLE ON SERVICE 2) WORK TO BE DONED BY LICENSED ELECTRICAL CONTRACTOR 3) MAST BRACE (PIPE) TO BE THREADED AT BOTH ENDS-DO NOT USE CONNECTORS 4) TIGHTEN GROUND ROD A CORNS 5) SEAL ROOF FLASHING 6) MAST BRACE FEET TO CONNECT TO STRUCTURE (TRUSSES) NOT JUST ROOF SHEATHING 7) SECURE GFI ENCLOSURE TO STRUCTURE 8) PROVIDE LADDER FOR ROOF ACCESS 9) NEED TO PAY REINSPECTION FEE 10) BURY GROUNDING ELECTRODE CONDUCTOR BETWEEN RODS |
|
09/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT USE COMPRESSION CONNECTORS TO CONNECT CONDUIT TO MAST BRACING. CONDUIT TO BE THREADED AT BOTH ENDS-NEC 110.3 2) CANNOT SEE LISTING MARK ON GROUND ROD THAT WAS ? NEED TO INSTALL NEW GROUND ROD 3) REMOVE PAINT AT GROUND CLAMP CONNECTION TO WATER PIPE NEC 250.12 |
|
09/25/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT -- NEC 230.28 2. GROUND RODS TO BE MIN. 6' APART - NEC 250.53 & 250.56 3. GROUND ROD BY PANEL APPEARS TO BE CUT 4. NEED TO BOND GAS & WATER PIPING - NEC 250.104 5. REMOVE EXCESS ANTI-OXIDATION COMPOUND 6. SECURE OUTLET BOX TO BUILDING SURFACE |