Permit: T07EL01670

Parcel: 113111680


Addresses:

1824 E WAVERLY ST


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01670

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
11/13/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL ADDRESS CABLE ON SERVICE
2) WORK TO BE DONED BY LICENSED ELECTRICAL CONTRACTOR
3) MAST BRACE (PIPE) TO BE THREADED AT BOTH ENDS-DO NOT USE CONNECTORS
4) TIGHTEN GROUND ROD A CORNS
5) SEAL ROOF FLASHING
6) MAST BRACE FEET TO CONNECT TO STRUCTURE (TRUSSES) NOT JUST ROOF SHEATHING
7) SECURE GFI ENCLOSURE TO STRUCTURE
8) PROVIDE LADDER FOR ROOF ACCESS
9) NEED TO PAY REINSPECTION FEE
10) BURY GROUNDING ELECTRODE CONDUCTOR BETWEEN RODS
09/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT USE COMPRESSION CONNECTORS TO CONNECT CONDUIT TO MAST BRACING. CONDUIT TO BE THREADED AT BOTH ENDS-NEC 110.3
2) CANNOT SEE LISTING MARK ON GROUND ROD THAT WAS ? NEED TO INSTALL NEW GROUND ROD
3) REMOVE PAINT AT GROUND CLAMP CONNECTION TO WATER PIPE NEC 250.12
09/25/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE
SMASHED EMT -- NEC 230.28
2. GROUND RODS TO BE MIN. 6' APART - NEC 250.53 & 250.56
3. GROUND ROD BY PANEL APPEARS TO BE CUT
4. NEED TO BOND GAS & WATER PIPING - NEC 250.104
5. REMOVE EXCESS ANTI-OXIDATION COMPOUND
6. SECURE OUTLET BOX TO BUILDING SURFACE