Permit: T07EL01664

Parcel: 123122350


Addresses:

1301 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/21/2007 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/20/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COVER WALL AND INSTALL SWITCH PLATES IN GARAGE BY NEW DOOR-OK WIRING
2) SMOKE DETECTORS IN BEDROOMS TO CLOSE TO VENTS, MUST BE AT 3' AWAY MIN. FROM VENTS OR REGISTERS, BETWEEN 6"-12" BELOW CEILING
3) OK ROOF ELECTRICAL
4) RECALL INSPECTION
09/18/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
GARAGE
1. LIGHT FIXTURES IN GARAGE CEILING NOT WIRED PER CODE
2. SOME BOXES TO FAR BACK BY NEW DOOR. USE APPROVED BOX EXTENDERS ALSO REMOVE NEW DRYWALL FOR INSPECTION OF WIRING (GARAGE) REPAIR RECEPT IN CEILING

HOUSE
1. INSTALL SMOKE DETECTORS IN ALL BEDROOMS
2. INSTALL COVER PLATE ON RECEPT & BOX IN WATER HTR. CLOSET ALSO, IN LIVING ROOM
3. PROVIDE LADDER FOR ROOF INSPECTION
09/14/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT OPEN PANEL AT MAIN (STUCK CLOSED) TO VERIFY ELECTRICAL SAFE TO RELEASE