Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LOCKNUT ON CONNECTOR AT BACK OF JUNCTION BOX FOR SUB-PANEL FEED - NEC 300.10 2. NEED MIN. 6" OF FREE CONDUCTOR LENGTH AT 6" X 6" JUNCTION BOX - NEC 300.14 3. RECALL WHEN READY |