Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEIVED MONEY ORDER #57149845434 FOR $150.00 2) FINISH PREVIOUS ITEMS 6 & 7 |
|
| 10/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT ENOUGH WORK DONE TO INSPECT |
|
| 10/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ED 403-0238 1. MAX 6'7" BREAKER HEIGHT 2. PROVIDE BETTER SUPPORT (BRACE) FOR MAST 3. BOND GAS PIPE 4. NEED PROPER CONNECTOR FOR FEEDER ENTERING PANEL 5. SEAL ROOF FLASHING 6. A PERMIT IS NEEDED FOR NEW AC AND NEW INTERIOR WIRING (ADDITION) 7. J-BOX TO BE RAINTITE 8. DRIVE GROUND RODS FLUSH |