Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/14/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UL LISTED DEAD FRONT REQUIRED 2) SCREW INTO PANEL MUST HAVE BLUNT END, NO SHARP EDGES (SELF TAPPING SCREW) 3) PROVIDE SAFE ACCESS TO ROOF 4) STOPPED INSPECTION 5) 250.114 NEC 2005' |
|
| 09/12/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FUSES IN SUB-PANEL OVERSIZED - SHOULD BE 20 AMP OR 15 AMP DEPENDING ON BRANCH CIRCUIT WIRE SIZE. 2. DEAD FRONT MISSING ON SERVICE PANEL. AC SYSTEM NOT GROUNDED, GROUND PER REQUIREMENTS NEC 250 3. RECEPT ON ROOF MUST BE RATED FOR OUTDOOR USE. |