Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - PLAN CALLS FOR #4 GROUNDING ELECTRODE CONDUCTOR - INSTALL ADDITIONAL GROUND ROD 6' MIN. FROM 1ST ROD - COMPLETE HOOK UP TO IRRIGATION CONTROLLER |