Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01641
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE METER TO BE SECURED TO BUILDING STRUCTURE 2. NUMEROUS HAZARDS & VIOLATIONS THROUGHOUT UNIT HAVE QUALIFIED ELECTRICIAN GO THROUGH UNIT AND CORRECT ALL HAZARDS & VIOLATIONS 3. ENSURE SMOKE DETECTORS ARE INSTALLED IN BEDROOMS AND OUTSIDE BEDROOMS PER MANUFACTURES INSTRUCTIONS 4. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 5. BATHROOM RECEPTACLES TO BE GFI PROTECTED 6. NEED TO COMPLY WITH DNR VIOLATIONS & CORRECTIVE ACTIONS PRIOR TO POWER BEING RESTORED |