Permit: T07EL01635

Parcel: 13622010A


Addresses:

7617 E 38TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CUT STRAND ON GROUNDING CONDUCTOR
2. GROUNDING CONDUCTOR TO TERMINATE IN SINGLE LUG LISTED FOR SIZE OF CONDUCTOR.
09/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUND BAR. INSTALL MANUFACTURES GROUND BAR AS LISTED ON PANEL COVER
2. INSTALL ANTI-OXIDATION COMPOUND OR ALUMINUM TERMINATIONS
3. CONDUCTORS LARGER THAN #10 INSTALLED IN RACEWAYS TO BE STRANDED