Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRALS #6 & SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6 2. EQUIPMENT GROUND TO BE RAN IN CONDUIT WITH CKT CONDUCTORS - NEC 300 & 250 3. SHEETMETAL SCREW NOT ALLOWED FOR LUG CONNECTION NEC 250 4. REMOVE PAINT UNDER LUG - NEC 250 5. GROUND METAL J-BOXES NEED TO PAY REINSPECTION FEE |
|
| 03/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP CONDUCTORS TO STRUCTURE 2. GROUND J-BOXES 3. NEUTRALS TO BE WHITE ENTIRE LENGTH |