Permit: T07EL01623

Parcel: 126121320


Addresses:

4610 E 7TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GAS BOND TO INTERIOR SIDE OF PIPING
2. OPEN METER SOCKET TO INSPECT

#6 PREVIOUS INSPECTION
09/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NOTE: UNIT IS ENERGIZED WITHOUT CLEARANCE

1. FILL UNUSED OPENINGS IN JUNCTION BOX
2. BONDING JUMPER TO BE SIZED PER 250.66
3. BOX & COVER TO BE LOCKABLE, ALSO LB & COVER
4. PLEASE VERIFY GROUNDING ELECTRODE SYSTEM
5. PLEASE VERIFY GAS & WATER BONDS
6. OPEN METER SOCKET TO INSPECT PER 250.92
7. A PERMANENT METAL ADDRESS LABEL IS NEEDED
8. SECURE CABLE TO BACK OF BOX 312.5
09/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DUE TO ROUTING SCHEDULE OF TIME ARE NOT AVAILABLE
CANCELLED
09/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TOO MANY WIRES UNDER TERMINATION FOR GROUND AND NEUTRAL CONDUCTOR
2. RACEWAY OVERFILLED
3. SUPPORT RACEWAY AS PER CODE
4. MAINTAIN SERVICE DROP CLEARANCE TO GROUND 230.24
5. PLEASE VERIFY TEP'S ALLOWANCE OF OLD METER SOCKET