Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GAS BOND TO INTERIOR SIDE OF PIPING 2. OPEN METER SOCKET TO INSPECT #6 PREVIOUS INSPECTION |
|
| 09/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTE: UNIT IS ENERGIZED WITHOUT CLEARANCE 1. FILL UNUSED OPENINGS IN JUNCTION BOX 2. BONDING JUMPER TO BE SIZED PER 250.66 3. BOX & COVER TO BE LOCKABLE, ALSO LB & COVER 4. PLEASE VERIFY GROUNDING ELECTRODE SYSTEM 5. PLEASE VERIFY GAS & WATER BONDS 6. OPEN METER SOCKET TO INSPECT PER 250.92 7. A PERMANENT METAL ADDRESS LABEL IS NEEDED 8. SECURE CABLE TO BACK OF BOX 312.5 |
|
| 09/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DUE TO ROUTING SCHEDULE OF TIME ARE NOT AVAILABLE CANCELLED |
|
| 09/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TOO MANY WIRES UNDER TERMINATION FOR GROUND AND NEUTRAL CONDUCTOR 2. RACEWAY OVERFILLED 3. SUPPORT RACEWAY AS PER CODE 4. MAINTAIN SERVICE DROP CLEARANCE TO GROUND 230.24 5. PLEASE VERIFY TEP'S ALLOWANCE OF OLD METER SOCKET |