Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL GROUNDING ELECTRODE FROM GROUND ROD TO DISCONNECT FOR SERVICE #1 2) RECALL WHEN READY |
|
| 09/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RECALL WHEN READY |
|
| 09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE CUT AND MISSING. NEED TO INSTALL NEW GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONDUCTOR PER NEC 250 III 2. INSTALL MISSING WALL PLATES FOR RECEPTACLES/SWITCHES 3. BATHROOM RECEPTACLE TO BE GFI PROTECTED 4. INSTALL CONNECTORS ON WIRES ENTERING PANEL 5. OUTDOOR WALL SCONCE HAS TOP REMOVED FILLED WITH INSECTS & WATER. PLEASE REPAIR. |