Permit: T07EL01622

Parcel: 11204200B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL GROUNDING ELECTRODE FROM GROUND ROD TO DISCONNECT FOR SERVICE #1
2) RECALL WHEN READY
09/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL WHEN READY
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE CUT AND MISSING. NEED TO INSTALL NEW GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONDUCTOR PER NEC 250 III
2. INSTALL MISSING WALL PLATES FOR RECEPTACLES/SWITCHES
3. BATHROOM RECEPTACLE TO BE GFI PROTECTED
4. INSTALL CONNECTORS ON WIRES ENTERING PANEL
5. OUTDOOR WALL SCONCE HAS TOP REMOVED
FILLED WITH INSECTS & WATER. PLEASE REPAIR.