| 09/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE - NEC 250.12 2. PROVIDE SAFE LEVEL WORK SURFACE IN FRONT OF SERVICE PANEL. REMOVE BOULDERS & TRIM/REMOVE TREE NEED 30" WIDE X 36" DEEP AREA -- NEC 110.26 |