Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL01621

Parcel: 134161150


Addresses:

7409 E 20TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE - NEC 250.12
2. PROVIDE SAFE LEVEL WORK SURFACE IN FRONT OF SERVICE PANEL. REMOVE BOULDERS & TRIM/REMOVE TREE
NEED 30" WIDE X 36" DEEP AREA -- NEC 110.26