Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 09/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 2. INSTALL PROPER SIZE BONDING JUMPERS - NEC 250.102 3. INSTALL PROPER SIZE EQUIPMENT GROUNDING CONDUCTORS -- NEC 250.122 4. INSTALL PROPER SIZE STRAPS ON 1 1/4" EMT |
|
| 09/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL FOR FINAL WHEN COMPLETE 2) LISTED MAST BRACE TO BE INSTALLED ASAP |