Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAX HEIGHT TO BREAKER 6'7" 2. BOND GAS & WATER -- NEC 250.104 3. INSTALL 2 GROUND RODS 6' APART 4. INSTALL PROPER SIZE JUNCTION BOXES AT SPLICE POINTS 6" X 6" X 4" NEMA 3R 5. PROPERLY SECURE EMT WITHIN 3' OF CONNECTION POINTS 6. INSTALL 2 POLE - 30 AMP BREAKERS FOR CONDUCTOR TO EXISTING FUSE BOXES 7. IDENTIFY NEUTRAL OF SERVICE CONDUCTORS. |