Permit: T07EL01617

Parcel: 107132580


Addresses:

414 E KELSO ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAX HEIGHT TO BREAKER 6'7"
2. BOND GAS & WATER -- NEC 250.104
3. INSTALL 2 GROUND RODS 6' APART
4. INSTALL PROPER SIZE JUNCTION BOXES AT
SPLICE POINTS 6" X 6" X 4" NEMA 3R
5. PROPERLY SECURE EMT WITHIN 3' OF CONNECTION POINTS
6. INSTALL 2 POLE - 30 AMP BREAKERS FOR CONDUCTOR TO EXISTING FUSE BOXES
7. IDENTIFY NEUTRAL OF SERVICE CONDUCTORS.