Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GAS PIPING NOT BONDED PROPERLY. ADD 2ND CLAMP AT WATER PIPE TO CONNECT BONDING JUMPER TO GAS PIPE 2) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 3) WIRE SIZE CHANGED TO 2/0 COPPER |
|
| 09/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION. NEC 110.3 2. SERVICE CONDUCTOR NOT SIZED PROPERLY NEED TO BE 2/0 COPPER OR 4/0 ALUMINUM FOR 200 AMP SERVICE. NEC 310.15 3. WATER BOND TO BE SIZED PER NEC 250.104 & 250.66 4. GAS PIPING TO BE BONDED PER NEC 250.104 5. BURY CONDUCTOR BETWEEN GROUND RODS AND SECURE CONDUCTOR TO BUILDING SURFACE 6. PVC PIPING TO BE SCH 80 WHEN RUN EXPOSED. LOCAL AMENDMENT. INSTALL PROPER FITTINGS AT CONNECTION PARTS. 7. SECURE RISER TO WOOD JUST BELOW ROOF LINE USE 1/4" HARDWARE TO SCHEDULE AFTER HRS. INSP. CALL RAY MAJUTA 909-5184 |