Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL NEC 110.3 2. MAXIMUM HEIGHT ON POINT OF ATTACHMENT IS 10' NEC 230.26 3. MINIMUM CLEARANCE OF SERVICE CONDUCTORS ABOVE ROOF IS 18" - NEC 230.24(A) EXCEPTION #3 4. CANNOT VERIFY GAS & WATER BOND - NEC 250.104 5. IDENTIFY NEUTRAL AT TERMINATION IN METER - NEC 200.6 6. VERIFY PERMIT FOR NEW AC UNIT - PLEASE PROVIDE COPY OF PERMIT 7. PROPERLY IDENTIFY WHITE WIRE USED AS HOT CONDUCTOR PER NEC 200.6 & 200.7 IDENTIFICATION TO ENCIRCLE CONDUCTOR 8. PROVIDE DETAILED PANEL SCHEDULE NEC 408.4 9. PROVIDE LADDER FOR INSPECTION OF 8" X 8" JUNCTION BOX 10. SERVICE MAST NOT INSTALLED PLUMB. INSTALL IN WORKMANLIKE MANNER - NEC 110.12 11. SERVICE ENERGIZED PRIOR TO APPROVALS CANNOT SEE INTO METER SECTION |