Permit: T07EL01601

Parcel: 10705127A


Addresses:

809 W LAGUNA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPAIR/REPLACE LIGHT AT ENTRY DOOR & BACK DOOR
2. SECURE DISCONNECT FOR CONDENSING UNIT TO BUILDING
3. INSTALL COVER AT WIRING COMPARTMENT FOR CONDENSING UNIT
4. INSTALL MISSING CABLES ON LIGHT FIXTURES
5. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS
6. INSTALL MISSING SMOKE DETECTOR
7. VERIFY ALL KITCHEN COUNTER RECEPTACLES ARE GFI PROTECTED
8. VERIFY ALL BATHROOM RECEPTACLES ARE GFI PROTECTED