Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECTLY (LEGIBLE) IDENTIFY BOTH PANEL DIRECTORIES 2. #6 & SMALLER GROUNDS TO BE GREEN ENTIRE LENGTH 3. FEEDER RACEWAY TO BE MINIMUM 18" BELOW GRADE 4. NEED GROUND RODS FOR SUB-PANEL & BOND METAL PIPING 5. NEED PROPER GROUND BAR IN SUB-PANEL, SEPARATE NEUTRALS AND GROUNDS 6. MAKE PROPER REPAIRS TO BRANCH CKT INSULATION 7. REMOVE OLD/UNUSED EQUIPMENT HAVE 3 - #2 & 1 #6 ALL IN 1" PIPE? |