Permit: T07EL01593

Parcel: 127040440


Addresses:

5025 E 1ST ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK UNIT #1 & #2
10/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE PROVIDE ACCESS TO INSPECT INTERIOR CONNECTIONS
09/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECALL AFTER CROSS OVER
09/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. RISER HARDWARE TO BE 1/4" MINIMUM
2. GROUNDING ELECTRODE TO TERMINATE TO GROUNDED TERMINAL
3. BOND RISER
4. AN APPROVED MAST BRACE KIT IS NEEDED
5. PLEASE VERIFY WATER BOND

OK 1 1/4" PVC CONDUIT TO COVER