Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/10/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* - NOT READY - USE RIGID CONDUIT FOR RISER, MUST BE THREADED INTO HUB, USE LISTED RISER BRACE FOR ROOF SUPPORT, ALSO - 2 GROUND RODS REQUIRED 6' MIN. APART BOND WATER & GAS PIPING - USE BUSHING FOR WIRING THRU BACK OF PANEL - ALSO, ADDRESS WIRING WITH EXPOSED SPLICES & CONDUCTORS |
|
| 09/06/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UPGRADE SERVICE PER CODE 2. RECEPTACLE ON OUTSIDE WALL NOT RATED FOR OUTSIDE USE ALSO DAMAGED 3. OTHER WIRING AROUND PREMISES UNSAFE - NOT PER CODE EXPOSED WIRING ON VARIOUS DEVICES LIGHT FIXTURES 4. OBTAIN THE SERVICES OF A LICENSED OR QUALIFIED ELECTRICIAN TO MAKE REPAIR. |