Permit: T07EL01577

Parcel: 125040980


Addresses:

1016 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION
1. USE SEALING TYPE LOCKNUTS INSTEAD OF SILICON FOR RACEWAY BETWEEN ENCLOSURES - NEC 110
2. CONDUCTORS IN 2" EMT TO BE DERATED FOR AMPACITY
NEC 310.15 B2
3. PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT
NEC 408.4
4. TWO NEUTRALS NOT ALLOWED UNDER SAME SCREW
NEC 408.41
5. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH
NEC 200.6
6. PROVIDE EQUIPMENT GROUND FOR SUB-PANEL
NEC 250
7. NEUTRALS TO BE ISOLATED FROM SUB-PANEL ENCLOSURE
NEC 250.24 A5
8. GROUND & NEUTRAL NOT TO TERMINAL UNDER SAME SCREW - NEC 408.41
9. INSTALL MISSING SERVICE DEAD FRONT COVER SCREW
10. PROVIDE LADDER AND INTERIOR ACCESS

WORK TO BE DONE BY QUALIFIED ELECTRICIAN