Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION 1. USE SEALING TYPE LOCKNUTS INSTEAD OF SILICON FOR RACEWAY BETWEEN ENCLOSURES - NEC 110 2. CONDUCTORS IN 2" EMT TO BE DERATED FOR AMPACITY NEC 310.15 B2 3. PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT NEC 408.4 4. TWO NEUTRALS NOT ALLOWED UNDER SAME SCREW NEC 408.41 5. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6 6. PROVIDE EQUIPMENT GROUND FOR SUB-PANEL NEC 250 7. NEUTRALS TO BE ISOLATED FROM SUB-PANEL ENCLOSURE NEC 250.24 A5 8. GROUND & NEUTRAL NOT TO TERMINAL UNDER SAME SCREW - NEC 408.41 9. INSTALL MISSING SERVICE DEAD FRONT COVER SCREW 10. PROVIDE LADDER AND INTERIOR ACCESS WORK TO BE DONE BY QUALIFIED ELECTRICIAN |