Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL 2 GROUND RODS MIN. 6' APART CANNOT DRIVE A #4 REBAR INTO GROUND AND USE AS A GROUNDING ELECTRODE. |
|
| 08/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GROUNDING ELECTRODE CONDUCTOR CUT & MISSING INSTALL PER SECTION III ART 250 OF NEC |