Permit: T07EL01540

Parcel: 131031310


Addresses:

5102 E 26TH ST

Inspection Status: Closed

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/24/2008 ELECTRIC - FINAL Closed
08/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/24/2007 ELECTRIC - FINAL Not ready for Inspection
08/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND CLAMPS TO BE LISTED & MARKED FOR DIRECT BURY AND FOR USE ON GROUND RODS -- NEC 250.70
2. MIN. HEIGHT ON POINT OF ATTACHMENT TO BE 10'
NEC 230.26
3. IDENTIFY NEUTRAL CONDUCTOR -- NEC 200.6
4. BOND GAS PIPING - NEC 250.104
5. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL
NEC 110.3
6. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING SURFACE -- NEC 250.64
7. IS 2 POLE 60 REQUIRED FOR RANGE? WHAT IS RANGE RECEPT RATED FOR? WHAT IS RANGE RATING?
SEE NEC 210.21
8. WHERE DO ROMEX (NEW) GO TO? NEED TO SEE FOR INSPECTION
9. SERVICE ENERGIZED PRIOR TO APPROVALS. CANNOT SEE INTO METER SECTION.