Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2008 | ELECTRIC - FINAL | Closed | ||
| 08/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | ||
| 08/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND CLAMPS TO BE LISTED & MARKED FOR DIRECT BURY AND FOR USE ON GROUND RODS -- NEC 250.70 2. MIN. HEIGHT ON POINT OF ATTACHMENT TO BE 10' NEC 230.26 3. IDENTIFY NEUTRAL CONDUCTOR -- NEC 200.6 4. BOND GAS PIPING - NEC 250.104 5. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL NEC 110.3 6. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING SURFACE -- NEC 250.64 7. IS 2 POLE 60 REQUIRED FOR RANGE? WHAT IS RANGE RECEPT RATED FOR? WHAT IS RANGE RATING? SEE NEC 210.21 8. WHERE DO ROMEX (NEW) GO TO? NEED TO SEE FOR INSPECTION 9. SERVICE ENERGIZED PRIOR TO APPROVALS. CANNOT SEE INTO METER SECTION. |