Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PLEASE HAVE ELECTRICIAN CALL ME 349-5029 |
|
| 10/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BRACES FOR MAST TO CONNECT TO MAST WITHIN 12" OF WEATHERHEAD AND LAG BOLT INTO ROOF TRUSSES (THREADED WITH FEET) 2. IDENTIFY NEUTRAL AS IT LEAVES WEATHERHEAD 3. SECURE TO STRUCTURE & BURY GROUNDING ELECTRODE CONDUCTOR, DRIVE RODS FLUSH TO GRADE 4. BOND GAS PIPE TO SERVICE 5. SECURE SERVICE TO STRUCTURE BETTER - USE SOMETHING OTHER THAN PLASTIC ANCHORS (NOT EFFECTIVE) |