Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01529
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER TO WATER PIPING TO BE SIZED PER NEC 250.104(A)(1) 2. BONDING JUMPERS TO BOND BUSHINGS TO BE SIZED PER NEC 250.102 (D) 3. PROVIDE ACCESS TO PANELS FOR ALL UNITS 4. EQUIPMENT GROUNDING CONDUCTORS TO 8" X 8" JUNCTION BOXES TO BE SIZED PER NEC 250.122 5. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH NEC 250.119 6. MARK "SERVICE DISCONNECTS" PER NEC 230.70 |