Permit: T07EL01529

Parcel: 13109188C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01529

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING JUMPER TO WATER PIPING TO BE SIZED PER
NEC 250.104(A)(1)
2. BONDING JUMPERS TO BOND BUSHINGS TO BE SIZED PER NEC 250.102 (D)
3. PROVIDE ACCESS TO PANELS FOR ALL UNITS
4. EQUIPMENT GROUNDING CONDUCTORS TO 8" X 8" JUNCTION BOXES TO BE SIZED PER NEC 250.122
5. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH NEC 250.119
6. MARK "SERVICE DISCONNECTS" PER NEC 230.70