Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER TEP TIE IN FOR ALL 4 UNITS 2) MARK SERVICE DISCONNECT PER NEC 230.70 |
|
| 09/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER TO WATER PIPING TO BE SIZED PER NEC 250.104(A)(1) 2. BONDING JUMPERS TO BOND BUSHINGS TO BE SIZED PER NEC 250.102 (D) 3. PROVIDE ACCESS TO PANELS FOR ALL UNITS 4. EQUIPMENT GROUNDING CONDUCTORS TO 8" X 8" JUNCTION BOXES TO BE SIZED PER NEC 250.122 5. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH NEC 250.119 6. MARK "SERVICE DISCONNECTS" PER NEC 230.70 |