Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01525
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF SERVICE EQUIPMENT - NEC 110.26 2. NEED TO INSTALL 4 WIRE CIRCUIT FOR ALL NEW DRYER CIRCUITS -- NEC 250.134 & 250. 138 3. INSTALL PROPER SIZE EQUIPMENT GROUNDING CONDUCTOR PER NEC 250.122 4. SECURE METAL FLEX PER NEC 348.30 |