Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01524
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WHAT HAPPENED TO THE RISER SUPPORT BELOW ROOF OVERHANG? HOLES STILL THERE BUT STRAP GONE. |
|
| 09/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE WATER PIPING UNDER SERVICE PANEL OR RELOCATE SERVICE 110.26 SEE NOTE #5 |
|
| 08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - USE OWN ACORN CLAMP FOR NEW #4 EXTENSION TO SECOND GROUND ROD - SEE NOTE #5 110.26 NEC - STRAP #4 BARE TO WALL |
|
| 08/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY 2 GROUND RODS (EXPOSE 2ND ROD) 2. BOND GAS PIPING 3. PLUG UNUSED OPENINGS 4. SERVICE TO HIGH ABOVE GRADE 6"-7" MAX. TO HIGHEST BREAKER 5. 30" HORIZONTAL X 36" IN FRONT DEDICATED WORKING SPACE, NO OBSTRUCTIONS IN THIS AREA 6. VERIFY RISER CONDUCTORS ARE SUNLIGHT RESISTANT 7. NO LOADS CONNECTED |