Permit: T07EL01524

Parcel: 14020001A


Addresses:

4948 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01524

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WHAT HAPPENED TO THE RISER SUPPORT BELOW ROOF OVERHANG? HOLES STILL THERE BUT STRAP GONE.
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE WATER PIPING UNDER SERVICE PANEL
OR RELOCATE SERVICE 110.26 SEE NOTE #5
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- USE OWN ACORN CLAMP FOR NEW #4 EXTENSION TO SECOND GROUND ROD
- SEE NOTE #5 110.26 NEC
- STRAP #4 BARE TO WALL
08/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY 2 GROUND RODS (EXPOSE 2ND ROD)
2. BOND GAS PIPING
3. PLUG UNUSED OPENINGS
4. SERVICE TO HIGH ABOVE GRADE 6"-7" MAX. TO HIGHEST BREAKER
5. 30" HORIZONTAL X 36" IN FRONT DEDICATED WORKING SPACE, NO OBSTRUCTIONS IN THIS AREA
6. VERIFY RISER CONDUCTORS ARE SUNLIGHT RESISTANT
7. NO LOADS CONNECTED