Permit: T07EL01518

Parcel: 134101470

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
10/01/2007 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
08/20/2007 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
1) NEED TO DERATE AMPACITY OF CONDUCTORS IN 1 1/2" EMT 10-20 CURRENT CARRING CONDUCTORS REQUIURES 50 PERCENT DERATION-NEC 310.15 &310.16
2) REMOVE RUST AND PAINT AT GROUND CLAMP CONNECTIONS ON WATER AND GAS PIPE-NEC 250.12
3) RECALL AFTER TEP TIE IN