Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL DIRECTORY TO BE CORRECT, NEAT, LEGIABLE NEC 408.4 2) SECURE EMT TO ROOF NEC 110.13 B 3) GROUNDS #6 AND SMALLER TO BE GREEN 250.119 4) INCREASE GROUND PER NEC 250.122 B 5) CHECK J-BOX FILL NEC 314.16 6) GROUND LUG IN GUTTER-NO SELF TAP SCREW, REMOVE PAINT NEC 250.8 AND 250.12 |