Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 09/14/2007 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL INSPECTION WHEN COMPLETE |
|
| 08/27/2007 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES #1 #5 #6 |
|
| 08/15/2007 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL 2 GROUND RODS MIN. 6' APART -- NEC 250.56 & 250.53 2. EMT CONDUIT BODIES NEED TO BE ACCESSIBLE 3. COVERS TO CONDUIT TO BE ACCESSIBLE 4. INSTALL WEATHERPROOF COUPLINGS ON EMT EXPOSED TO WEATHER 5. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT & MINERALLAC STRAPS 6. BOND GAS & WATER PIPING PER NEC 250.104 7. INSTALL PROPER HUB AT SERVICE PANEL. NEED TO GET CUTLER HAMMER PARTS & ACCESSORIES. CANNOT USE SQUARE D HUB |
|
| 08/13/2007 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ANSWER AT DOOR DOGS IN BACKYARD RECALL INSPECTION |