Permit: T07EL01492

Parcel: 133367310


Addresses:

9930 E COLETTE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. 8-3 NM CABLE AMPACITY TO BE CODE
2. PLEASE VERIFY ALUMINUM CONDUCTOR SIZE AND AMPACITY
3. FINISH #3 & #4 PREVIOUS INSPECTION
09/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A PERMANENT METAL ADDRESS LABEL IS NEEDED
2. LABEL PANEL AS PER 408.4 -- NO ABBREVIATION & DISTINGUISHABLE FROM ONE ANOTHER
3. WHAT ARE NEW CIRCUITS ADDED - NOT ON PERMIT
4. PLEASE VERIFY PERMIT FOR NEW AC UNIT
5. USE APPROVED SPLICES FOR COPPER TO ALUMINUM
6. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE 250.92