Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. 8-3 NM CABLE AMPACITY TO BE CODE 2. PLEASE VERIFY ALUMINUM CONDUCTOR SIZE AND AMPACITY 3. FINISH #3 & #4 PREVIOUS INSPECTION |
|
| 09/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A PERMANENT METAL ADDRESS LABEL IS NEEDED 2. LABEL PANEL AS PER 408.4 -- NO ABBREVIATION & DISTINGUISHABLE FROM ONE ANOTHER 3. WHAT ARE NEW CIRCUITS ADDED - NOT ON PERMIT 4. PLEASE VERIFY PERMIT FOR NEW AC UNIT 5. USE APPROVED SPLICES FOR COPPER TO ALUMINUM 6. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE 250.92 |