Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RE-IDENTIFY WHITE WIRE IN CABLE ASSEMBLY USED A5 PHASE CONDUCTOR -- NEC 200.7 2. CONDUCTORS SMALLER THAN #6 USED AS GROUNDS & NEUTRALS NEED TO BE IDENTIFIED ALONG ENTIRE LENGTH. NEC 250.119 & 200.6 3. NEED TO INSTALL NEUTRAL CONDUCTOR FOR DRYER CIRCUIT. EXISTING 3 WIRE DRYER CIRCUITS CAN USE NEUTRAL CONDUCTOR FOR GROUNDING - NEC 250.140 4. SERVICE ENERGIZED PRIOR TO APPROVALS |