Permit: T07EL01489

Parcel: 135053090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RE-IDENTIFY WHITE WIRE IN CABLE ASSEMBLY USED A5 PHASE CONDUCTOR -- NEC 200.7
2. CONDUCTORS SMALLER THAN #6 USED AS GROUNDS & NEUTRALS NEED TO BE IDENTIFIED ALONG ENTIRE LENGTH.
NEC 250.119 & 200.6
3. NEED TO INSTALL NEUTRAL CONDUCTOR FOR DRYER CIRCUIT. EXISTING 3 WIRE DRYER CIRCUITS CAN USE NEUTRAL CONDUCTOR FOR GROUNDING - NEC 250.140
4. SERVICE ENERGIZED PRIOR TO APPROVALS