Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COVER PIPES OR CUT BELOW GRADE TO PREVENT TRIP HAZARD -- 110.26 2. LUG ON TOP OF WASHER ON TOP OF PAINT WITH DRYWALL SCREW NOT ALLOWED -- 250.8 & 250.12 |
|
| 08/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE CORRECT ADDRESS ON PERMIT 2) SOLIDLY ANCHOR RISER BRACE SUPPORTS 3) MAINTAIN WORKING CLEARANCE 110.26 4) LABEL PANEL AS PER 408.4-NO ABREVIATIONS 5) NO MORE THAN 360 DEGREE IN A CONDUIT RUN 6) IDENTIFY PHASE CONDUCTOR IN JUNCTION BOX TO VERIFY NEUTRAL TO PHASE LOADS 7) GROUND JUNCTION BOX 8) TIGHTEN LOOSE FITTINGS 9) SUPPORT CONDUITS AS PER CODE 10) A PERMANENT METAL ADDRESS LABEL IS NEEDED 11) BOND TO INTERIOR SIDE OF GAS PIPING |