Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLOSE WALL 1. FINISH COMPRESSOR |
|
| 11/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENING IN PANEL PLJ-2 NOT EMPTY FITTING 2. FINISH PREVIOUS ITEM #1,2,3,7 & 9 |
|
| 10/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. OPEN WALLS AT ELECTRIC RECEPTACLES PER INSPECTION OF 3/30/06 T06VL00509 2. RECEPTACLES IN SHOP AREA TO BE GFCI PROTECTED 511.12 3. MAINTAIN WORKING CLEARANCE PER 110.26 4. MISSING SET SCREWS FOR CONNECTOR BELOW PANEL PLJ-2 TIGHTEN BOTTOM FITTING 5. INSTALL GROUNDING EQUIPMENT CONDUCTOR AS PER MANUFACTURES INSTRUCTIONS 6. LABEL ALL BREAKERS 7. DISCONNECTING MEANS NEEDED FOR COMPRESSOR 8. CONDUCTOR NOT RATED FOR WET LOCATION 9. PLEASE VERIFY LISTING FOR COMPRESSOR *GAVE CUSTOMER COPIES OF PREVIOUS VIOLATION INSPECTIONS. |