Permit: T07EL01474

Parcel: 134160540


Addresses:

7270 E BEVERLY DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1. KNOCKED SEVERAL TIMES. NO ANSWER. UNABLE TO OPEN GATE & HAVE DOG IN YARD
2. RECALL WHEN READY
10/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MTG TO DISCUSS CORRECTIONS
09/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
08/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDS & NEUTRALS TO BE SEPARATE IN OLD PANEL NOW JUNCTION BOX. NEUTRALS CANNOT ALL BE CONNECTED TOGETHER. SPLICE NEUTRALS TOGETHER WITH WIRE NUTS
2. 10/3 ROMEX IS ONLY GOOD FOR 30 AMP MAX
3. PROTECT 3/4" EMT FROM CORROSION WHERE COVERED BY DIRT
4. HAVE EXPOSED LIVE PARTS IN OLD PANEL MAKE SPLICES BY USING WIRE NUTS NOT TERMINAL STRIP
5. REMOVE OLD CONNECTORS NOT BEING USED AT SEAL OPENINGS
6. EMT FITTINGS EXPOSED TO WEATHER NEED TO BE WEATHER TIGHT
7. PROPERLY BOND AROUND REDUCING WASHERS.
USE APPROVED FITTINGS FOR CONNECTION OF EMT TO PANELS NOT CHASE NIPPLES
8. METAL RACEWAYS TO BE METALLICALLY CONTINUOUS CANNOT USE NON-METALLIC
LIQUID TIGHT
USE APPROVED FITTINGS.