Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. KNOCKED SEVERAL TIMES. NO ANSWER. UNABLE TO OPEN GATE & HAVE DOG IN YARD 2. RECALL WHEN READY |
|
| 10/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MTG TO DISCUSS CORRECTIONS |
|
| 09/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION |
|
| 08/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDS & NEUTRALS TO BE SEPARATE IN OLD PANEL NOW JUNCTION BOX. NEUTRALS CANNOT ALL BE CONNECTED TOGETHER. SPLICE NEUTRALS TOGETHER WITH WIRE NUTS 2. 10/3 ROMEX IS ONLY GOOD FOR 30 AMP MAX 3. PROTECT 3/4" EMT FROM CORROSION WHERE COVERED BY DIRT 4. HAVE EXPOSED LIVE PARTS IN OLD PANEL MAKE SPLICES BY USING WIRE NUTS NOT TERMINAL STRIP 5. REMOVE OLD CONNECTORS NOT BEING USED AT SEAL OPENINGS 6. EMT FITTINGS EXPOSED TO WEATHER NEED TO BE WEATHER TIGHT 7. PROPERLY BOND AROUND REDUCING WASHERS. USE APPROVED FITTINGS FOR CONNECTION OF EMT TO PANELS NOT CHASE NIPPLES 8. METAL RACEWAYS TO BE METALLICALLY CONTINUOUS CANNOT USE NON-METALLIC LIQUID TIGHT USE APPROVED FITTINGS. |