Permit: T07EL01472

Parcel: 11703189A


Addresses:

724 N MAIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS METER IN FRONT OF SERVICE, NEC 2005 REQUIRES CLEARANCE DOWN TO GRADE AND 3' AWAY
2. STRAP GROUNDS ON WALL
3. HIGH LEG TO BE ON C PHASE FOR TEP AND B PHASE LOAD SIDES, AND TAPE ORANGE
4. #2 WIRE IS ONLY GOOD FOR 115 AMPS OR 125A
5. ONE STRAP BELOW LAST LB
6. SEAL TOP SIDE ENTRY ON 200 AMP DISCONNECT HAS TO BE WP ABOVE BUS LINE.
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE MAIN DISCONNECT, OUTDATED
ALSO, WATER DAMAGE
2. WHY IS NEW METER BASE CONNECTED TO OLD 60 AMP METER BASE?
3. NEUTRAL MUST BE RUN TO DISCONNECTING MEANS AT SERVICE.
4. VERIFY INTEGRITY OF GROUNDING ELECTRODE SYSTEM THRU QUALIFIED TEST AGENCY OR INSTALL NEW
5. WHEN INSTALLING #4 OR LARGER CONDUCTORS INSULATING BUSHINGS MUST BE USED AT TERMINATIONS
6. BE ADVISED THAT SEALABLE PULLING FITTINGS WITH COVERS ON SERVICE CONDUCTORS MAY BE REQUIRED
PER TEP