Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL LISTED MAST BRACING NEC 230.28 2) SEAL OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL 3) RECALL WHEN READY |