Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLOTHES CLOSET LIGHTS TO BE 100% ENCLOSED 2. INSTALL BATTERY POWERED SMOKE DETECTORS IN BEDROOMS AND AREA OUTSIDE BEDROOMS PER MANUFACTURES INSTRUCTIONS 3. BATHROOM RECEPTACLES TO BE GFI PROTECTED 4. CANNOT HAVE GROUNDING TYPE RECEPTACLES ON UNGROUNDED SYSTEM 5. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 6. INSTALL JUNCTION BOXES FOR WIRING OF OUTDOOR FIXTURES AT BACK DOUBLE DOOR & FLOOD LIGHT DRIVEWAY |