Permit: T07EL01455

Parcel: 113081940


Addresses:

1037 E HEDRICK DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2007 ELECTRIC - FINAL Approved
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE COMPRESSION CONNECTORS FOR CONNECTION OF MAST BRACING. PIPES NEED TO BE THREADED AT BOTH ENDS.
2. SECURE #4 RUN ON ROOF
3. PROVIDE INFORMATION ON GROUND CLAMPS USED ON GROUND RODS ARE LISTED TO BE USED ON GROUND RODS
4. ALL CONDUCTORS FOR BRANCH CIRCUIT FEEDERS
NEED TO BE INSTALLED IN SAME RACEWAY
NEED TO INSTALL GROUNDING CONDUCTOR IN EACH RACEWAY
5. NEED TO INSTALL NEUTRAL CONDUCTOR FOR SUB-PANEL
BARE CONDUCTOR IN OLD CABLE ASSEMBLY IS NEUTRAL CONDUCTOR NOT GROUNDING CONDUCTOR
6. CANNOT USE SHEET METAL SCREWS FOR CONNECTION OF EQUIPMENT GROUNDS
7. DO NOT SEE MARKING ON SERVICE CONDUCTORS THAT THEY ARE SUNLIGHT RESISTANT. PLEASE VERIFY.
8. CANNOT SEE CONNECTIONS IN METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVALS.