Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2007 | ELECTRIC - FINAL | Approved | ||
| 08/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE COMPRESSION CONNECTORS FOR CONNECTION OF MAST BRACING. PIPES NEED TO BE THREADED AT BOTH ENDS. 2. SECURE #4 RUN ON ROOF 3. PROVIDE INFORMATION ON GROUND CLAMPS USED ON GROUND RODS ARE LISTED TO BE USED ON GROUND RODS 4. ALL CONDUCTORS FOR BRANCH CIRCUIT FEEDERS NEED TO BE INSTALLED IN SAME RACEWAY NEED TO INSTALL GROUNDING CONDUCTOR IN EACH RACEWAY 5. NEED TO INSTALL NEUTRAL CONDUCTOR FOR SUB-PANEL BARE CONDUCTOR IN OLD CABLE ASSEMBLY IS NEUTRAL CONDUCTOR NOT GROUNDING CONDUCTOR 6. CANNOT USE SHEET METAL SCREWS FOR CONNECTION OF EQUIPMENT GROUNDS 7. DO NOT SEE MARKING ON SERVICE CONDUCTORS THAT THEY ARE SUNLIGHT RESISTANT. PLEASE VERIFY. 8. CANNOT SEE CONNECTIONS IN METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVALS. |