Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MUST USE A LISTED RISER SUPPORT ON ROOF
2. BOLTS FOR RISER SUPPORT TO HOLD DOWN CLAMP TO SURFACE PUT SOMETHING BEHIND RISER
3. IF WHITE CONDUCTORS TO TIE INTO CIRCUIT BREAKERS THEY MUST BE PROPERLY COLOR CODED
4. PROPERLY TAPE SPLICED CONDUCTOR TO SUB-PANEL
5. WHERE IS WATER BOND?
6. ROMEX NOT TO BE PULLED THRU CONDUIT
7. ADDRESS SERVICE