Permit: T07EL01452

Parcel: 140372880

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ELECTRICAL CONTRACTOR STATED HE WAS GOING TO REPLACE EXISTING SERVICE PANEL WITH NEW SUB-PANEL
2) RECALL AFTER TEP TIE IN AND OLD SERVICE PANEL REPLACED
3) BOND TO WATER PIPE IS NO GOOD. LINE UNDER HOUSE IS PVC. CHECK TO SEE IF HOUSE HAS METAL WATER PIPE INSTALLED
08/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROPER SIZE MINERALLAC STRAPS ON 2 1/2" RISER
2. PROVIDE LISTING INFORMATION ON EXISTING PANEL
BELIEVE IT IS LISTED FOR USE AS ONLY SERVICE EQUIPMENT AND CANNOT BE USED AS SUB-PANEL. THERE IS NO WAY TO SEPARATE GROUNDS AND NEUTRALS AT THIS PANEL IT BEING ALL IN ONE ENCLOSURE
3. GROUND RODS OK
4. GAS & WATER BOND OK