Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ELECTRICAL CONTRACTOR STATED HE WAS GOING TO REPLACE EXISTING SERVICE PANEL WITH NEW SUB-PANEL 2) RECALL AFTER TEP TIE IN AND OLD SERVICE PANEL REPLACED 3) BOND TO WATER PIPE IS NO GOOD. LINE UNDER HOUSE IS PVC. CHECK TO SEE IF HOUSE HAS METAL WATER PIPE INSTALLED |
|
| 08/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROPER SIZE MINERALLAC STRAPS ON 2 1/2" RISER 2. PROVIDE LISTING INFORMATION ON EXISTING PANEL BELIEVE IT IS LISTED FOR USE AS ONLY SERVICE EQUIPMENT AND CANNOT BE USED AS SUB-PANEL. THERE IS NO WAY TO SEPARATE GROUNDS AND NEUTRALS AT THIS PANEL IT BEING ALL IN ONE ENCLOSURE 3. GROUND RODS OK 4. GAS & WATER BOND OK |