Inspection History Details
Inspection Status: Cancelled
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
| 10/02/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/16/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT HAVE PROPER WORKING CLEARANCES IN FRONT OF SERVICE PANEL - NEC 110.26 2. CANNOT EXIT LOAD CONDUCTORS THROUGH TOP END WALL PER MANUFACTURES INSTRUCTIONS - NEC 110.3 3. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH - NEC 200.6 4. EQUIPMENT GROUNDING CONDUCTORS TO BE CONNECTED BY LISTED MEANS - NEC 250.8 5. PROVIDE LADDER FOR INSPECTION 6. GROUNDS & NEUTRALS TO BE SEPARATE AT GUEST HOUSE NEC 250.32 7. INSTALL 2 GROUND RODS MIN. 6' APART AT GUEST HOUSE NEC 250.32 8. LABEL CIRCUITS AT GUEST HOUSE - NEC 408.4 9. DO NOT HAVE PROPER CLEARANCE TO GROUND ON FEEDER CONDUCTORS TO GUEST HOUSE -- NEC 225.18 10. DO NOT HAVE PROPER POINT OF ATTACHMENT & CLEARANCES, DRIP LUGS - NEC 225.16 11. NEED DISCONNECT AT GUEST HOUSE - NEC 225.31 & 32 12. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 13. SERVICE CONDUCTORS APPEAR DAMAGED BY WEATHERHEAD. |