Permit: T07EL01427

Parcel: 111070950


Addresses:

2632 N SPARKMAN BL

Inspection Status: Cancelled

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/02/2007 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled
10/02/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/16/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DO NOT HAVE PROPER WORKING CLEARANCES IN FRONT OF SERVICE PANEL - NEC 110.26
2. CANNOT EXIT LOAD CONDUCTORS THROUGH TOP END WALL PER MANUFACTURES INSTRUCTIONS - NEC 110.3
3. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH - NEC 200.6
4. EQUIPMENT GROUNDING CONDUCTORS TO BE CONNECTED BY LISTED MEANS - NEC 250.8
5. PROVIDE LADDER FOR INSPECTION
6. GROUNDS & NEUTRALS TO BE SEPARATE AT GUEST HOUSE
NEC 250.32
7. INSTALL 2 GROUND RODS MIN. 6' APART AT GUEST HOUSE
NEC 250.32
8. LABEL CIRCUITS AT GUEST HOUSE - NEC 408.4
9. DO NOT HAVE PROPER CLEARANCE TO GROUND ON FEEDER CONDUCTORS TO GUEST HOUSE -- NEC 225.18
10. DO NOT HAVE PROPER POINT OF ATTACHMENT & CLEARANCES, DRIP LUGS - NEC 225.16
11. NEED DISCONNECT AT GUEST HOUSE - NEC 225.31 & 32
12. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
13. SERVICE CONDUCTORS APPEAR DAMAGED BY WEATHERHEAD.