Permit: T07EL01421

Parcel: 125111130


Addresses:

3618 E 2ND ST #03

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/07/2007 ELECTRIC - FINAL Denied NOT READY
WHEN A SERVICE IS UPGRADED IT REQUIRE AN UPGRADE PERMIT
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE OVERHEAD WIRING FEEDING THIS UNIT #3 ARE GOING OVER AND RESTING ON THE ROOF OF #2
2. INSIDE PANEL DOUBLE LUGGING NOT ALLOWED ON TERMINATIONS, WHITE WIRE CANNOT BE USED AS HOT CONDUCTOR
3. PANEL NOR APT. #3 HAS A GROUNDED SERVICE
4. SMOKE DETECTOR NEEDS BATTERY
5. RECEPTACLES ARE OFF 3-HOLE TYPE INDICATING GROUNDS - WIRING SYSTEM HAS NO GROUND
NEED TO GO BACK TO 2 HOLE
6. SINK RECEPTACLE NEEDS TO BE GFI
7. WIRING IN MAIN 30 AMP CB CRACKED INSULATION IMPROPER UNWEATHERPROOF WIRING ABOVE METER
8. NO WATER OR GAS BONDING TO SERVICE
9. SERVICE SYSTEM OLD & DILAPIDATED - UNSAFE
TO RENERGIZE - YOU WILL NEED TO UPGRADE SERVICE