Permit: T07EL01417

Parcel: 136344730


Addresses:

7301 E NICARAGUA DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REVISE FOR SERVICE UPGRADE
2. BOND OFFSET NIPPLE & RISER PER NEC 250.92 & 250.66
3. BOND GAS & WATER PIPING - NEC 250.104
4. INSTALL MAIN BONDING JUMPER
5. MARK "SERVICE DISCONNECT"
6. CANNOT USE WHITE WIRE FOR EQUIPMENT GROUND
7. PROTECT WIRES THROUGH BACK OF OLD PANEL & SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL
8. SEAL OPEN KNOCK OUT IN OLD PANEL
9. PROPERLY STRAP SEAL TIGHT & EMT AT OLD PANEL
10. SECURE #4 TO BUILDING SURFACE
11. PANEL DIRECTORY NEC 408.4
12. PLAN CALLS FOR 200 AMP. SERVICE
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS. LEAVE INSTRUCTIONS FOR NEXT INSPECTION.
2. INSTALL MAIN BONDING JUMPER AT SERVICE PANEL
NEC 250.28
3. INSTALL GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES - NEC 210.8
4. VERIFY ALL BATHROOM RECEPTACLES ARE GFI PROTECTED NEC 210.8
5. DO NOT HAVE PROPER WORKING CLEARANCE AT SERVICE PANEL -- NEC 110.26
6. VERIFY PERMIT FOR ADDITION TO BACK OF HOME
NEW LAUNDRY ROOM