Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REVISE FOR SERVICE UPGRADE 2. BOND OFFSET NIPPLE & RISER PER NEC 250.92 & 250.66 3. BOND GAS & WATER PIPING - NEC 250.104 4. INSTALL MAIN BONDING JUMPER 5. MARK "SERVICE DISCONNECT" 6. CANNOT USE WHITE WIRE FOR EQUIPMENT GROUND 7. PROTECT WIRES THROUGH BACK OF OLD PANEL & SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL 8. SEAL OPEN KNOCK OUT IN OLD PANEL 9. PROPERLY STRAP SEAL TIGHT & EMT AT OLD PANEL 10. SECURE #4 TO BUILDING SURFACE 11. PANEL DIRECTORY NEC 408.4 12. PLAN CALLS FOR 200 AMP. SERVICE |
|
| 08/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS. LEAVE INSTRUCTIONS FOR NEXT INSPECTION. 2. INSTALL MAIN BONDING JUMPER AT SERVICE PANEL NEC 250.28 3. INSTALL GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES - NEC 210.8 4. VERIFY ALL BATHROOM RECEPTACLES ARE GFI PROTECTED NEC 210.8 5. DO NOT HAVE PROPER WORKING CLEARANCE AT SERVICE PANEL -- NEC 110.26 6. VERIFY PERMIT FOR ADDITION TO BACK OF HOME NEW LAUNDRY ROOM |