Permit: T07EL01416

Parcel: 12511247C


Addresses:

655 N ALVERNON WY

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/03/2007 ELECTRIC - FINAL Partial Approval 1ST INSPECTION PROPERLY DEAD END ALL CONDUITS WITH OPEN WIRING, REMOVE ALL DAMAGED FIXTURES, CONDUITS AND ELECTRICAL ITEMS DAMAGED, ISOLATE AND WATERPROOF OPENING ABOVE C-2 PNL 2ND FLOOR

2ND INSPECTION ALL ITEMS ABOVE CORRECTED BY CASCADE
OK TO ENERGIZE REST OF PANEL, CIRCUITS ISOLATED ALL DAMAGED WIRING REMOVED, DAMAGED LIGHTING REMOVED
PERMIT TO FOLLOW FOR REPAIRS.
07/30/2007 ELECTRIC - FINAL Partial Approval SOUTHERNMOST ATRIUM 2ND FLOOR SOFFIT SYSTEM HAS COLLAPSED, DOWNED SOFFIT LIGHTING INCLUDING OTHER WIRING FEEDING 2ND FLOOR.

ELECTRICAL CONTRACTOR HAS OK TO ENERGIZE NORTH 1/2
MAIN SWITCH GEAR AND FOLLOWING PNLS ENERGIZED
PNL L-A, PNL-A, TRANS TI, LB, RI, R-2, B, 2B

PNLS C AND PNL 2C TO REMAIN OFF
PNL L-B, 2LB OFF NOW, TO BE ENERGIZED

ONCE CASCADE REVIEWS - CASCADE ELECT.
PARTY RESPONSIBLE ON ELECTRICAL .

THIS INSPECTION IS NOT FOR ANY TYPE OF OCCUPANCY,
DSD TO REVIEW PRIOR TO ANY TYPE OF OCCUPANCY.

CALL FOR INSPECTION 7/31/07
AFTER HRS. FEE COLLECTED ON SITE