Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRIVE 2ND GROUND ROD FLUSH WITH GRADE 8' IN GROUND PER 250 NEC. 2. CHANGE DESCRIPTION ON PERMIT TO 100 AMPS 3. NEED TO VERIFY GAS BOND. DOORS LOCKED HOUSE NOT OCCUPIED 4. GROUND WIRE SPLICED TO NEUTRAL IN J-BOX? NEUTRAL SHOULD BE CONSISTENT TO NEUTRAL BAR IN PANEL |