Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER SUPPORT REQUIRED PER 230 NEC 2. BOND BUSHINGS REQUIRED WHERE USING RE-WASHERS AT TERMINATIONS INTO PANEL PER 250 NEC 3. TWIN BREAKER NOT TERMINATED 4. OK TWO GROUND RODS & WATER & GAS BONDING 5. INSTALL PERMANENT ADDRESS LABEL ON SERVICE. |